[Vwdiesel] Fw: Power Generation --- ( electrical )
Shirley, Mark R
MarkRShirley at eaton.com
Thu Apr 15 08:56:35 EDT 2004
Rather than replacing all your appliances with DC appliances, it would
likely make a lot more sense to just install a big inverter on your
battery bank, so that when you have to replace a DC appliance, you don't
have to wait 3 weeks for one to be mailed to you...
> -----Original Message-----
> From: gary [mailto:gbangs at cfl.rr.com]
> Sent: Wednesday, April 14, 2004 9:03 PM
> To: VWDiesel
> Subject: Re: [Vwdiesel] Fw: Power Generation --- ( electrical )
>
>
> Hmmm,
>
> Are we talking about a lightly loaded windmill with a strong breeze?
>
> Windmills attempt to maintain 60hz (well, here in the US) by either
> changing the generator field strength, and/or blade angle. The smaller
> gensets will only adjust the field, the monstrous ones will do both.
>
> Your 63hz windmill doesn't have enough load to maintain frequency.
> But that doesn't mean that it cannot be connected though.
>
> Synchronize it with and connect to the grid. Boom! Rock steady 60 hz.
> Why, because the generating capacity of the grid dictates the
> frequency.
> Your puny (no disrespect intended) windmill does not have
> enough umph to
> change system frequency.
>
> Your genset controller, either manually or automatically, will attempt
> to adjust its voltage and frequency. Ideally, as a small
> generator, you
> want the 'set' voltage slightly higher than grid voltage.
> Reason is that
> as a generator, you want amps to flow out, not in. This also reduces
> "recirculating" current... VA power which does nothing, compared to
> Watts, real power.
>
> What really makes your windmill make power is the freq setting. By
> setting the 'set' freq higher than grid, though freq will
> stay steady at
> 60hz, the phase angle of your generated power will lead the grid phase
> angle. This makes power flow out. On the other hand, you can make your
> windmill a big "fan" by setting the set freq lower than grid.
>
> Note, when doing all of this, you need to know the Kw and amp
> limits of
> your machine and adjust your settings accordingly.
>
> You can run your house on DC! Of course! Why not?
>
> You would of course need to replace ALL of your appliances with a DC
> powered equivalent. Replace ALL of your outlets with the
> appropriate DC
> version. In this day and age, I would suspect that it would be cost
> prohibitive to do.
>
> -Gary
>
>
>
> On Wed, 2004-04-14 at 10:44, Val Christian wrote:
> > Gary,
> >
> > So what happens if you generate power at 63 Hz, so that it can't
> > be put on the grid. How's about running your house on DC?
>
>
> _______________________________________________
> Vwdiesel mailing list
> Vwdiesel at vwfans.com
> http://www.audifans.com/mailman/listinfo/vwdiesel
>
More information about the Vwdiesel
mailing list